Troubleshooting

Communication lost with internal Digi radio

Most of the time, the communication between Autopilot 1x and Digi radio is lost due to a change in its baudrate.

In 1x PDI Builder it is set to 115200 by default, however, in Digi radios the factory default baudrate at reset is 9600.

To recover communication, try changing the baudrate on one of them to match.

  1. Go to Input/Output menu \(\rightarrow\) Serial panel \(\rightarrow\) Veronte LOS tab.

    Set the Baudrate on Veronte LOS to 9600.

    ../_images/digi_radio_veronte_los_baudrate.png

    Veronte LOS baudrate

  2. Check the steps described in the Digi internal radio - Integration examples section to see if the module is now detected in XCTU software.

    Then, if desired, the user can change the radio baudrate to 115200 and after that also change it for Veronte Autopilot 1x.

Debug serial messages transmission

To check that the transmission of serial messages is being carried out correctly, the user can view what is being sent in the 1x PDI Calibration software hyperterminal. To do this:

1x PDI Builder side

  1. Go to Input/Output menu \(\rightarrow\) I/O Setup panel.

    Connect the RS custom message producer (where the message is configured) to a Tunnel with App2 address. In this case, the message is configured in the RS custom message 1 producer.

    ../_images/debug_serial_messages_io.png

    RS custom message \(\rightarrow\) Tunnel

In 1x PDI Calibration side

  1. Go to Terminal tab.

    Click on Agree:

    ../_images/debug_serial_messages_terminal.png

    Terminal tab

  2. Next, select the Tunnel 1 (this is the one that has been configured in 1x PDI Builder) and click on Launch:

    ../_images/debug_serial_messages_terminal_tunnel.png

    Terminal tab - Tunnel selected

    The tunnel console should open and the user will be able to view the message being sent:

    ../_images/debug_serial_messages_tunnel_console.png

    Tunnel console

    For more information on the Terminal configuration, please refer to the Terminal section of the 1x PDI Calibration user manual.

Maintenance mode

The user can simply enter maintenance mode via 1x PDI Builder by clicking on the “Normal mode” button in the initial menu. In addition, exiting maitenance mode is the same process.

Below is an example of how to do this:

../_images/enter_maintenance_mode.gif

Enter/Exit maintenance mode

Maintenance mode (loaded with errors)

The following error message may appear when trying to save a change or import a configuration.

../_images/loaded_with_errors_message.png

Error message

Therefore, Veronte Autopilot 1x will be in ‘Maintenance mode (loaded with errors)’:

../_images/loaded_with_errors.png

Maintenance mode (loaded with errors)

To check what the source of the problem is, the user can simply click on the PDI Error button pdi_errors, which will show what the PDI Error is:

../_images/loaded_with_errors_pdi_errors_panel.png

Maintenance mode (loaded with errors) - PDI Errors panel

  • PDI ID: ID of the PDI Error.

  • PDI Error Description: Description of this PDI Error. A list of all PDI Errors can also be accessed in the List of PDI errors section of the 1x Software Manual.

  • Config ID: ID of the configurable (.xml file) containing the data in which the PDI Error has been caused.

  • Config Description: Description of the configurable (.xml file) containing the data in which the PDI Error has been caused.

Clicking the Export button will export a .csv file with the same information shown in this PDI Errors panel.

This is useful while the configuration is in progress, however, if the user encounters this situation during the operation, it is also possible to look up the cause of the PDI Error directly on the Platform panel of Veronte Ops. For more information about this panel, see Platform panel section of the Veronte Ops user manual.

../_images/loaded_with_errors_veronte_ops.png

PDI Error - Veronte Ops

Then, it is possible to access the Autopilot 1x configuration to fix this error.

Tip

If the PDI error is related to a migration, it is usually caused by the selection of accelerometer, gyroscope and magnetometer sensors.

In addition, a list of all PDI Errors can be accessed in the List of PDI errors section of the 1x Software Manual.

Migrate configuration

Warning

When performing automatic migration from a previous version to the current version of the software, errors may occur.

It is then the responsibility of the user to check the subsequent result.

Radios paired but 1x air unit not showing

If the radios of both Autopilots 1x, air and ground unit, are paired but the air unit does not appear connected in Veronte Link, check the Ports configuration on the 1x ground unit. To do this:

Go to Communications menu \(\rightarrow\) Ports panel, and it should be similar to the configuration shown in the figure below:

../_images/1x_ground_configuration.png

1x ground unit - Ports configuration

Reducing GNC Task frequency

400 Hz is the maximum possible frequency, but can only be used in simple configurations, in other cases it is advisable to reduce it to 250-300 Hz.

To find out if the frequency needs to be reduced in the user configuration, check the GNC Task Average CPU Ratio variable.

For correct operation, this variable should be at approximately 60-70%. If it reports a higher value, the frequency must be lowered.

Trajectory Overshoot

If the user observes significant meandeling or overshoot in the mission path, this can be reduced by modifying the gains of the guidance PIDs:

  • Reducing the proportional gain.

  • Ensure that the integral gain is 0.

Guidance error accumulates and leads to increasing overshoot, as can be seen in the following example:

../_images/trajectory_overshoot.png

Trajectory overshoot